[From:来自网络] [Author:admin] [Date:11-09-21] [Hit:]
- Set up the valve, I/P positioner, current source generator, and instrument air supply as shown in the control valve functional test setup file in the end of this article.
- Check the pressure of the instrument air supply. Make sure it has been according to the I/P Positioner requirements.
- Apply 4 mA current signal to the I/P positioner. Check the valve stem travel indication, the valve stem shall be in 0% travel. Apply 20 mA current signal to the I/P positioner. Check the valve stem travel indication, the valve stem shall be in 100% travel.
- If the valve stem travel indication didn’t show correctly 0% or 100% travel, then calibrate the stem travel by using the HART communicator (follow the instruction of the I/P positioner manufacturer). This travel calibration normally will determine the position of 0% and 100% travel + the hysteresis and or linearity correction.
- Check the five point stem travel (for hysteresis and linearity check) from 0%, 25%, 50%, 75%, 100% and then 100%, 75%, 50%, 25% and 0%.
- Check the three point stem travel (for deadband check on 5%, 50%, and 95% stem travel).
- Record the result in the below form for the hysteresis, linearity, and deadband error check.
- Repeat the step 4 if the hysteresis and or the linearity of the valve travel exceed the acceptance criteria.
- If the deadband error exceed the acceptance criteria, contact the valve manufacturer for further solution (the valve may require some reparation)
Hysteresis, Linearity, and Deadband Check Form
- 4-20 mA current source generators
- HART communicator
- Instrument air connection
- Screwdriver set
- Wrench set
- Hex key set
This typical functional test procedure is just an illustration of how to regularly test a control valve for academic purpose only. This typical procedure shall not be used as day to day operation guidance. The vendor specific manual shall be used in detail.